RTS-ABAC:面向变电站自动化系统的实时服务器辅助属性基授权与访问控制 RTS-ABAC: Real-Time Server-Aided Attribute-Based Authorization & Access Control for Substation Automation Systems 预印本

⚠️ 本文为 预印本(arXiv 公开版本),尚未经过正式同行评审。作者自发公开,结论未经期刊审稿验证,阅读时请知悉。
发布时间:2026-03-24
👁️ 预览文献
💡 AI 中文简介
针对变电站自动化系统(SAS)在IEC 61850等标准下缺乏细粒度访问控制的问题,提出RTS-ABAC方案。它引入实时属性和时间相关策略,采用旁路部署方式对GOOSE、SV等通信进行强制认证与授权。测试表明,99.82%的数据包往返时延低于6毫秒,既能保障低延迟通信安全,也可用于现有变电站改造。
领域工业控制系统安全 / 电力系统通信安全
适合谁读需要一定专业背景(电力自动化、网络安全领域读者)
核心贡献1. 提出融合实时属性与时间相关策略的ABAC扩展模型,满足SAS严格时延要求;2. 设计基于旁路(BITW)的强制认证授权机制,可兼容现有及新建变电站。
关键数据99.82%的数据包往返时延低于6毫秒;在GOOSE和SV协议下通过智能电子设备、合并单元和I/O箱验证了适用性。
推荐理由如果你关心电力系统实时安全,这篇论文给出了兼顾低延迟和强访问控制的实用方案,实测数据亮眼,值得一读。
关键词["变电站自动化系统", "属性基访问控制", "实时安全", "IEC 61850", "GOOSE/SV", "旁路部署"]

原文摘要

查看英文原文摘要

Critical energy infrastructures increasingly rely on information and communication technology for monitoring and control, which leads to new challenges with regard to cybersecurity. Recent advancements in this domain, including attribute-based access control (ABAC), have not been sufficiently addressed by established standards such as IEC 61850 and IEC 62351. To address this issue, we propose a novel real-time server-aided attribute-based authorization and access control for time-critical applications called RTS-ABAC. We tailor RTS-ABAC to the strict timing constraints inherent to the protocols employed in substation automation systems (SAS). We extend the concept of conventional ABAC by introducing real-time attributes and time-dependent policy evaluation and enforcement. To safeguard the authenticity, integrity, and non-repudiation of SAS communication and protect an SAS against domain-typical adversarial attacks, RTS-ABAC employs mandatory authentication, authorization, and access control for any type of SAS communication using a bump-in-the-wire (BITW) approach. To evaluate RTS-ABAC, we conduct a testbed-based performance analysis and a laboratory-based demonstration of applicability. We demonstrate the applicability using intelligent electronic devices, merging units, and I/O boxes communicating via the GOOSE and SV protocol. The results show that RTS-ABAC is able to secure low-latency communication between SAS devices, as up to 99.82 % of exchanged packets achieve a round-trip time below 6 ms. Moreover, the results of the evaluation indicate that RTS-ABAC is a viable solution to enhance the cybersecurity not only in a newly constructed SAS but also via retrofitting of existing substations.