强化学习与模型预测建筑控制中舒适度作为约束或成本 Comfort as a Constraint or as a Cost in Reinforcement Learning and Model Predictive Building Control 预印本

⚠️ 本文为 预印本(arXiv 公开版本),尚未经过正式同行评审。作者自发公开,结论未经期刊审稿验证,阅读时请知悉。
发布时间:2026-11-16
👁️ 预览文献
💡 AI 中文简介
本研究比较了建筑温控中舒适度作为软约束(加权违反成本)和硬约束(严格限制)对能耗的影响。在BOPTEST热泵案例上,分别用模型预测控制(MPC)和强化学习(RL)测试。结果发现:硬约束能耗更高但舒适度违反更少;大权重下软约束接近硬约束行为;三种加权控制器的能耗-舒适度权衡前沿相近,权重决定工作点。对于该暖通空调问题,问题表述和权重比算法选择对能耗影响更大。
领域建筑能源管理/智能控制
适合谁读需要一定专业背景(控制理论、强化学习基础)
核心贡献1. 系统分离了问题表述(软/硬约束)与算法选择对能耗和舒适度的影响;2. 揭示了在软约束下不同RL算法(SAC、DDPG)与MPC能达到相近的能耗-舒适度权衡前沿。
关键数据硬约束能耗高于软约束(最大权重时),但舒适度违反更少;软约束在大权重下逼近硬约束行为;三种加权控制器前沿接近,权重选择工作点;算法间差异小于表述和权重的影响。
推荐理由如果你在纠结建筑控温该用硬约束还是软约束,这篇论文用数据告诉你:表述和权重比选什么算法更重要。
关键词["强化学习", "模型预测控制", "建筑控制", "舒适度约束", "能耗优化", "暖通空调"]

原文摘要

查看英文原文摘要

A building controller that keeps a zone within comfort bounds at minimum energy can treat the bounds as a soft constraint, by adding the weighted violation to its cost, or as a hard constraint. We analyze the effect of the hard and the soft formulation of the same problem and isolate the effect of the formulation from the effect of the algorithm. To this end, we measure the difference in energy use between the two formulations on the BOPTEST bestest_hydronic_heat_pump case, in model predictive control (MPC) and in reinforcement learning (RL). The soft formulations are a weighted MPC and weighted SAC and DDPG learners, each at twelve weights. The hard formulations are an MPC with an exact penalty and the Lagrangian learners SAC-Lagrangian and primal-dual DDPG. We find that the hard formulations use more energy than the soft formulations at the largest weight, but violate the comfort bounds less. For a large weight, the soft formulation approaches the behavior of the hard formulation. The frontiers of the energy-comfort trade-off of the three weighted controllers lie close to each other, and the weight selects an operating point on this frontier. Under the soft formulation, the three algorithms reach very similar operating points, although at somewhat different weights. For this HVAC problem, the formulation and the weight thus affect the energy use more than the choice of algorithm.