深度强化学习在暖通空调监督控制中何时见效?基于FMU直接训练的四项小型Modelica案例研究 When does deep reinforcement learning pay off in HVAC supervisory control? Four small Modelica case studies trained directly on FMUs 预印本

⚠️ 本文为 预印本(arXiv 公开版本),尚未经过正式同行评审。作者自发公开,结论未经期刊审稿验证,阅读时请知悉。
发布时间:2026-11-17
👁️ 预览文献
💡 AI 中文简介
本研究通过四个基于澳大利亚布里斯班办公楼的Modelica仿真案例,探讨深度强化学习(DRL)在暖通空调监督控制中的实际效果。研究将DRL智能体与调优规则控制器及近乎最优参考(动态规划或穷举搜索)对比,发现无储能的案例中DRL仅略优于规则(1.3%和0.18%),有储能的案例中DRL优于规则但仅达完美预见节能的45%,预冷案例中规则反而更优(-12.0% vs -5.6%)。结论建议DRL研究应报告与最优参考的差距,并分享了在FMU上训练的实际困难。
领域建筑能源系统与智能控制
适合谁读需要一定专业背景(暖通空调、强化学习或能源系统建模)
核心贡献1. 通过四个可复现的小型案例,量化了DRL相对于调优规则和近乎最优参考的实际性能差距;2. 指出DRL在HVAC控制中的收益高度依赖场景(如储能存在与否),并报告了在FMU上直接训练的实际困难。
关键数据无储能案例:冷凝水重置DRL仅优于规则1.3%,冷冻水重置仅0.18%;有储能案例:DRL节能7.8%,规则节能3.9%和6.3%,但仅达完美预见节能的45%;预冷案例:规则节能12.0%,DRL仅5.6%。
推荐理由如果你关心DRL在真实能源系统中到底能省多少,这篇用硬数据告诉你:别只看相对规则的提升,还要看离最优有多远。
关键词["深度强化学习", "暖通空调控制", "Modelica仿真", "规则控制器", "近乎最优参考", "储能优化"]

原文摘要

查看英文原文摘要

Deep reinforcement learning (DRL) is often proposed for the supervisory control of heating, ventilation and air-conditioning (HVAC) systems. The reported gains are, however, difficult to interpret, because the baselines are often weak and the attainable optimum is seldom known. This paper examines four small, reproducible case studies based on an office building in Brisbane, Australia: pre-cooling under a time-of-use tariff; chiller staging with condenser water reset; chilled water supply temperature reset with a wet cooling coil; and chilled water storage under time-of-use prices and a demand charge. The plants were modelled with the Modelica Buildings library, and in three of the cases a soft actor-critic agent was trained directly on the exported functional mock-up unit (FMU). Each agent was compared with tuned rule-based controllers and, where practicable, with a near-optimal reference from hourly exhaustive search or dynamic programming with perfect foresight. In the two cases without storage the agent reached the near-optimal reference, but the margin above a well-chosen rule was small: 1.3% for condenser water reset and 0.18% for chilled water reset. In the latter case two common reset rules consumed more energy than a fixed set point. With a chilled water storage tank the margin was considerably larger. The agent outperformed both rules (-7.8%, compared with -3.9% and -6.3%) and adopted midday charging during the solar off-peak period, yet it obtained only about 45% of the saving achieved by the perfect-foresight schedule and did little to limit the demand peak. In the pre-cooling case a hand-tuned rule remained superior (-12.0% compared with -5.6%). These results suggest that studies of DRL for HVAC control should state the margin between the best rule and a near-optimal reference. Some practical difficulties encountered in training on co-simulation FMUs are also reported.